Storage and transportation requirements
Ambient temperature: -30~65℃
Relative humidity: 0~95%
Ambient pressure: 86~106kPa
System should be placed vertically upward during storage and transportation
Keep power interfaces protected in order to prevent collision, which may cause short circuit during the process of storage and transportation
System must be charged to rated voltage before long term storage and transportation. Check cell voltage difference every 45 days, when cell voltage difference is<200mV and >50mV, balance system should be activated until the cell voltage difference drops to ≤40mV, when cell voltage difference is>200mV, child node or capacitor should be checked, replace the bad child node or cell if necessary
When system is kept unused for longer than 1 year, it should be tested by Aowei before using.
Avoid contacting corrosive materials, keep away heat sources and fire sources
Prevent violent vibration, collision or crush during the process of transportation
Prevent exposing in the sun and rain, and keep dry and ventilated during transportation
The system can be transported by cars, trains, ships, etc